TGOV1
TGOV1 model
This article is incomplete, some sections must be written.
Context
This governor model appears under the name GovSteam0 in the Common Information Model for Dynamics - Standard Models (2012) (missing reference) and in the IEC 61970-302:2024 version (Commission, 2024).
Model use, assumptions, validity domain and limitations
To be completed
Model inputs and output
The input variables are :
Variable | Description | Units |
---|---|---|
omegaPu | measured angular frequency | pu (base omegaNom) |
omegaRefPu | reference angular frequency | pu (base omegaNom) |
PmRefPu | reference mechanical power | pu (base PNomTurb) |
The output signal is PmPu, the mechanical power in pu (base PNomTurb).
Model parameters
Parameter | Description | Units |
---|---|---|
Dt | Turbine damping coefficient | pu |
R | Permanent droop | pu |
t1 | Steam bowl time constant | s |
t2 | Reheater lead time constant | s |
t3 | Reheater lag time constant | s |
VMax | Maximum valve position | pu |
VMin | Minimum valve position | pu |
Model diagram
Open source implementations
This model has been successfully implemented in :
Software | URL | Language | Open-Source License | Last consulted date | Comments |
---|---|---|---|---|---|
Dynawo | Link | Modelica | MPL v2.0 | 24/05/2024 |
References
- Commission, I. E. (2024). Energy management system application program interface (EMS-API) Part 302: Common information model (CIM) dynamics. IEC 61970-302. https://webstore.iec.ch/preview/info_iec61970-302%7Bed2.0%7Db.pdf