IEEEG1 GovSteam 1

IEEEG1 model / GovSteam 1

Context

This governor was initially developed and described in (on Prime Mover, 1973). It is oftenly combined with the LCFBA model which is a simple representation of an outer-loop MW controller.

This governor model appears under the name GovSteam1 in the Common Information Model for Dynamics - Standard Models (2012) (missing reference) and in the IEC 61970-302:2024 version (Commission, 2024).

Model use, assumptions, validity domain and limitations

It includes the rate limits on the main control valve (Uo and Uc) as well as four steam‐stages and the ability to model cross‐compound Units. There are a number of key assumptions behind this model:

  • steam pressure and temperature remain constant under all conditions,
  • the unit is in boiler‐follow control mode – that is, the main steam control valve (MCV) is used primarily for regulating power and the boiler follows the turbine in producing additional steam as needed, and
  • there is essentially an unlimited source of steam from the boiler to be provided once the main steam control valve opens. These assumptions are quite simplistic and not truly indicative of the physics of a steam turbine. However, it can be true for many steam turbines such as boiler‐follow control.

As stated in (system dynamic performance committee Task Force on Turbine-Governor Modeling, 2013), it has been been shown that this model in combination with LCBF1 is effective in capturing the behavior of large steam turbine generators that are operated on outer‐loop MW control. It applicable for large interconnected grid simulations when looking at relatively small frequency deviations, that is, in the range of +/‐ 0.5% change in frequency. The LCBF1 model is needed only in cases where there is a active secondary outer‐loop MW controller in the plant.

Model inputs and output

The input variables are :

Variable Description Units
omegaPu measured angular frequency pu (base omegaNom)
omegaRefPu reference angular frequency pu (base omegaNom)
PmRefPu reference mechanical power pu (base PNomTurb)

The output signal is PmPu, the mechanical power in pu (base PNomTurb).

Model parameters

Variable Description Units
K Governor gain (reciprocal of droop) pu
K1 Fraction of HP shaft power after first boiler pass -
K2 Fraction of LP shaft power after first boiler pass -
K3 Fraction of HP shaft power after second boiler pass -
K4 Fraction of LP shaft power after second boiler pass -
K5 Fraction of HP shaft power after third boiler pass -
K6 Fraction of LP shaft power after third boiler pass -
K7 Fraction of HP shaft power after fourth boiler pass -
K8 Fraction of LP shaft power after fourth boiler pass -
PMaxPu Power output of boiler at maximum valve opening pu (base PNomTurb)
PMinPu Power output of boiler at minimum valve opening pu (base PNomTurb)
t1 Governor lag time constant s
t2 Governor lead time constant s
t3 Valve positioner time constant s
t4 HP bowl time constant s
t5 Reheater time constant s
t6 Crossover time constant s
t7 Double reheat time constant s
Uc Maximum valve closing velocity pu/s (base PNomTurb)
Uo Maximum valve opening velocity pu/s (base PNomTurb)

Model diagram

IEEEG1 diagram

Open source implementations

This model has been successfully implemented in :

Software URL Language Open-Source License Last consulted date Comments
Dynawo Link Modelica MPL v2.0 24/05/2024  

References

  1. on Prime Mover, I. E. E. E. W. G. (1973). Dynamic Models for Steam and Hydro Turbines in Power System Studies. IEEE Trans. on PAS, Vol PAS-92. https://ieeexplore.ieee.org/document/141700/authors#authors
  2. Commission, I. E. (2024). Energy management system application program interface (EMS-API) Part 302: Common information model (CIM) dynamics. IEC 61970-302. https://webstore.iec.ch/preview/info_iec61970-302%7Bed2.0%7Db.pdf
  3. system dynamic performance committee Task Force on Turbine-Governor Modeling, P. (2013). Dynamic Models for Turbine-Governors in Power System Studies. IEEE Power & Energy Society PES-TR1 Technical Report. https://site.ieee.org/fw-pes/files/2013/01/PES_TR1.pdf