IEEX2A

Authors: Erwan Guichard (DPS for RTE)

Reviewers: Mathilde Bongrain (CRESYM)

This article is incomplete, some sections must be written.

Context

To be completed

Model use, assumptions, validity domain and limitations

To be completed

Model inputs and output

The input variables are :

Variable Description Units
UsPu measured stator voltage pu (base UNom)
UsRefPu reference stator voltage pu (base UNom)
UOelPu (optional) output voltage of overexcitation limiter pu (base UNom)
UPssPu (optional) output voltage of power system stabilizer pu (base UNom)
UUelPu (optional) output voltage of underexcitation limiter pu (base UNom)

The output signal is EfdPu, the excitation voltage in pu (user-selected base voltage).

Model parameters

Parameter Description Units
AEx Gain of saturation function pu
BEx Exponential coefficient of saturation function -
EfdMinPu Minimum excitation voltage pu (user-selected base voltage)
Ka Voltage regulator gain pu
Ke Exciter field proportional constant pu
Kf Exciter rate feedback gain pu
tA Voltage regulator time constant s
tB Voltage regulator lag time constant s
tC Voltage regulator lead time constant s
tE Exciter field time constant s
tF1 Feedback lead time constant s
tR Stator voltage filter time constant s
VrMaxPu Maximum field voltage pu (user-selected base voltage)
VrMinPu Minimum field voltage pu (user-selected base voltage)

Model diagram

IEEX2A

Open source implementations

This model has been successfully implemented in :

Software URL Language Open-Source License Last consulted date Comments
Dynawo Link Modelica MPL v2.0 24/05/2024  

References

    Evaluate